AIR LEAKAGE IN MODELING

 

Residential: 

  • Multifamily Performance Program Requires residential to be:  0.35 Air Changes Per Hour.  See MPP Guidebook page 25.  This does not include the mechanical venilation initiated by the exhaust fan of a bathroom or kitchen.
  •  

 

Infiltec.com has a collection of links on air leakage studies.

 

The Below table is from infiltec.com (UK) and shows values of Leakage per surface area exposed per type of building. 

 

Table 1: ATTMA Air Leakage Index (m3/hr/m2 [cfm/ft2] @ 50Pa)

Building Type (UK buildings) Best Practice Leakage Index Normal Practice Leakage Index
Offices (naturally ventilated) 3.0 [0.1641] 7.0 [0.3828]
Offices (mixed mode ventilation) 2.5 [0.1367] 5.0 [0.2735]
Offices (air conditioned/low energy) 2.0 [0.1094] 5.0 [0.2735]
Factories/Warehouses 2.0 [0.1094] 6.0 [0.3281]
Superstores 1.0 [0.0547] 5.0 [0.2735]
Schools 3.0 [0.1641] 9.0 [0.4922]
Hospitals 5.0 [0.2735] 9.0 [0.4922]
Museums and Archival Stores 1.0 [0.0547] 1.5 [0.0828]
Cold Stores 0.2 [0.0109] 0.35 [0.0191]
Dwellings (naturally ventilated) 3.0 [0.1641] 9.0 [0.4922]
Dwellings (mechanically ventilated) 3.0 [0.1641] 5.0 [0.2735]